OPC UA write task
Write a value to an OPC UA node each time a command channel gets a new value.
An OPC UA write task writes a value to a node each time you write a value to a command channel. For example, a valve on a schematic can set a PLC setpoint. If you write several values at once, the task writes only the last one. The task writes single values, not arrays.
The task has no state channels. To see the value on the server, read the node back with an OPC UA read task. Before you start, you need a connected OPC UA server.
Create an OPC UA write task
When you create command channels with a client library, give each one its own index channel. A writer that holds several commands on one index must write all of them in every frame.
Console
Python
TypeScript
- In the devices toolbar, right-click the server and select Create write task.
- In the Browser, expand the folders of the server.
- Drag the variables to write into Channels.
- Click (Start).
The Console creates a command channel for each node, named <node>_cmd, and its index
<node>_cmd_time. To choose another name, right-click the channel and select Rename
before you start.
To add many nodes at once, drag a folder into Channels, or import a CSV file. See
find nodes. A write task CSV has no
index column, and the Console skips rows with a field.
Python does not create channels. Create the command channel and its index first.
import synnax as sy
from synnax import opcua
server = client.devices.retrieve(name="Line 1 PLC")
cmd_time = client.channels.create(
name="pump_setpoint_cmd_time", is_index=True, data_type=sy.DataType.TIMESTAMP
)
cmd = client.channels.create(
name="pump_setpoint_cmd", index=cmd_time.key, data_type=sy.DataType.FLOAT64
)
task = opcua.WriteTask(
name="Line 1 PLC write",
device=server.key,
channels=[
opcua.WriteChannel(cmd_channel=cmd.key, node_id="NS=2;S=Pump1.Setpoint")
],
)
client.tasks.configure(task)
task.start()TypeScript does not create channels. Create the command channel and its index first.
import { opcua } from "@synnaxlabs/client";
const [server] = await client.devices.retrieve({
where: { name: { eq: "Line 1 PLC" } },
});
const cmdTime = await client.channels.create({
name: "pump_setpoint_cmd_time",
isIndex: true,
dataType: "timestamp",
});
const cmd = await client.channels.create({
name: "pump_setpoint_cmd",
index: cmdTime.key,
dataType: "float64",
});
const task = await client.tasks.create({
name: "Line 1 PLC write",
rack: server.rack,
type: "opc_write",
config: opcua.writeConfigZ.parse({
device: server.key,
channels: [{ cmdChannel: cmd.key, nodeId: "NS=2;S=Pump1.Setpoint" }],
}),
});
await task.start();The OPC UA write task has one option, Auto start (auto_start), which starts the
task each time the Driver starts. For node IDs, see
node IDs. When a frame has more
commands than the server accepts in one request, the Driver splits the write into
smaller requests.
Channel reference
The table shows the Console label of each setting, with its Python field under it.
Data types
The Driver reads the type of each node when it connects, and converts each command to
that type. For example, a float64 channel can write 3 to an Int16 node, or 1 to a
Boolean node.
The Driver does not send a command that does not fit the node, such as 300 for a Byte
node or 1.5 for an Int16 node. The task shows
“Failed to write commands” and writes the other channels.
When the server does not give the type of a node, the Driver writes the value with the OPC UA type of the command channel:
A write task cannot write to a field of a structure node.
Troubleshooting
- Cause
The server did not give the type of the node, so the Driver wrote the type of the command channel, and the type does not match the node.
- Fix
Use the data type from the table. For example, a Double node needs a
float64channel.
- Cause
The server has no node with that ID.
- Fix
Drag the node from the Browser again.
- Cause
The server has no namespace with the URI in the node ID of the channel. The server can add the namespace later, for example when a PLC loads its program.
- Fix
Check that the server loaded its program, or drag the node from the Browser again.
- Cause
The node is read only on the server, or the user of the connection cannot write to it.
- Fix
Make the node writable on the server, or connect with a user that can write to it.
- Cause
The node ID is not in a form that the Driver accepts.
- Fix
Write the node ID in one of the forms in node IDs.
- Cause
The task could not write a command. The description names each channel and the reason. The task writes the other channels of the command and keeps running. When the connection is lost, the Driver connects again once and repeats the write, so a value that the server already got can arrive twice. If that fails, the task drops the command. It does not keep commands for later, because a late command could move hardware at the wrong time.
- Fix
Fix the cause in the description. For a lost connection, check the server connection. The next command connects again.
For other problems, see Troubleshoot hardware.