OPC UA read task

Read the values of OPC UA nodes at a fixed rate and record them in channels.

An OPC UA read task reads the values of nodes on a server at a fixed rate and records them in channels. For example, it can record the tank pressures and pump speeds of a PLC 50 times a second. The Driver times each read in software.

Before you start, you need a connected OPC UA server.

Node IDs

Each channel of the task reads one node. A node ID names the namespace of the node and its identifier, in one of these forms:

Form Example
nsu=<namespace URI>;<type>=<identifier> nsu=urn:example:plant;s=Tank1.Pressure
ns=<namespace index>;<type>=<identifier> ns=2;s=Tank1.Pressure
<type>=<identifier> i=2258, a node in namespace 0
Type Identifier Example
i A number ns=2;i=1001
s A string ns=2;s=Tank1.Pressure
g A GUID ns=2;g=09087e75-8e5e-499b-954f-f2a9603db28a
b Bytes, in base64 ns=2;b=M/RbKBsRVkePCePcx24oRA==

The browser in the Console fills node IDs in the nsu= form. A server can give a namespace a different index when it restarts, but the URI stays the same. In a URI, write ; as %3B and % as %25. The Driver ignores the case of the prefix and the type, so it also accepts NS=2;S=Tank1.Pressure.

Create an OPC UA read task

Enterprise
  1. In the devices toolbar, right-click the server and select Create read task.
  2. Set Sample rate and Stream rate.
  3. In the Browser, expand the folders of the server.
  4. Drag the variables to read into Channels. You can select more than one.
  5. Click (Start).

The Console creates a channel for each node, named from the browse name of the node. To choose a name, edit the name of the channel before you start. The Console also creates an index channel named <server>_time_for_<task>, unless one of the channels already has an index or you use server timestamps.

Find nodes

The Browser loads the children of a node when you expand it. It stops at 10,000 children, or after 7 seconds on a slow server, and the Console warns you when it stops early. To find a node:

  • Type in the filter field. The browser shows only the loaded nodes whose name or node ID holds the text. Expand a folder to load its nodes.
  • Type a node ID, such as ns=2;s=Tank1.Pressure, and press Enter. The browser reads that node, even if it is not loaded.

Select a node to see its node ID, class, data type, shape, access, and minimum sampling interval, with its current value, status, and timestamps. Click (Read again) to read the value again. You can drag a node by its name in the details into Channels. A node that fails to browse shows , with the reason when you hover over it. The rest of the tree stays.

Add a folder

Drag a folder or an object into Channels to add the variables under it, at any depth. The Console asks you to confirm the count before it adds them. It names each channel from the folder and the browse path below it, such as Line1_Tank1_Pressure. When the task already has the name, the Console adds a number, such as Line1_Tank1_Pressure_2. The Driver looks under objects, but not under variables. It stops after 1,000 variables, 10,000 objects, or 20 seconds, and the Console tells you when it stopped early.

Import and export channels

Click (Export channels to CSV) in Channels to save the channels as <task name>_channels.csv. Click (Import channels from CSV) to add the channels of a CSV file. The Console adds only the nodes that the task does not have. If one row is not valid, it adds nothing and names the row.

The file starts with a header row. Only node_id is required. Commas or tabs can separate the cells, and the Console ignores other columns.

Column Default Notes
name Empty The channel name. Empty uses the node name.
node_name Empty The node name. Empty uses the end of the node ID.
node_id See node IDs.
field Empty See structure fields.
data_type float32 A Synnax data type.
enabled true true or false.
index false true uses the node as the index.

Read arrays

Some servers buffer fast samples in an array node. To read the arrays:

  1. Set Sampling mode to Array.
  2. Set Array size to the number of values in each array.

The Driver then reads each node Sample rate / Array size times a second, and spreads the timestamps of the values evenly over the read period. Sample rate must be equal to or more than Array size. Each array must have exactly Array size values, or the Driver drops the frame and shows a warning. Stream rate does not apply in array mode.

Read structure fields

Some nodes hold a structure, such as a motor with a speed, a state, and a position. A channel can read one field of the structure:

  1. In the Browser, expand the structure node. The browser shows the fields of its type, and the fields of each nested structure.
  2. Drag the fields into Channels.

The Console names each channel <node>.<field>, such as Motor.Speed. The channels of one node share one read, so their values come from the same moment. The task reads the definition of the type from the server each time it connects. If the server does not give the definition, the task shows “Received bad values” for the fields of that type.

In Python and TypeScript, set field to the path of the field from the node, with . between names, such as Position.Y. Put & before a . or a & that is part of a name: a&.b is the field a.b.

Array mode cannot read structure fields. A write task cannot write to a field, so the Console does not add fields to a write task.

Use server timestamps

By default, the Driver gives the values of each read the time halfway through the read request. To use the time from the server instead:

  1. Add a node with a DateTime value, such as the source time of the PLC, to the task.
  2. Turn on Use as index for that channel.

The Driver then uses the value of that node as the timestamp of every channel in the task. Only one channel can be the index.

Bad values

The server sends a status with each value. The task records a value with a Good or an Uncertain status. For an Uncertain value, it also shows the warning “Received uncertain values” with the name of the channel.

The task does not record a Bad value. A node that does not exist and a value that the Driver cannot convert are Bad values too. The task shows the warning “Received bad values” with the name of the channel and the status, such as BadSensorFailure, and keeps running. When the value becomes good again, the task records it.

By default, a Bad value skips the sample for every channel on the same index. Turn on NaN fill to write NaN for a float channel instead, so that the other channels keep their samples. A line plot shows NaN as a gap. A Bad value of a channel that is not a float still skips its index.

Outages

A read task keeps running when the server or the network goes down. It shows “Failed to read data” and tries again at most 5 seconds apart. A task can also start while the server is off. Before each new connection, the task gets the connection settings of the server again, so a corrected endpoint or password takes effect without a restart.

Task options

Console label Python field Default Notes
OPC UA server device The key of the server.
Sampling mode sampling Scalar sy.opcua.ArraySampling(size=5) reads arrays. See read arrays.
Sample rate sample_rate 50 Hz (10 Hz in Python) Reads per second. At most 10,000.
Stream rate stream_rate 25 Hz (5 Hz in Python) Frames per second sent to the Core. At most the sample rate. Not in array mode.
Array size sampling.size 1 Values in each array node.
NaN fill nan_fill_enabled Off See bad values.
Data saving data_saving_disabled On See data saving.
Auto start auto_start Off Starts the task each time the Driver starts.

TypeScript uses the same fields in camel case, such as sampleRate. See timing. When a task has more nodes than the server accepts in one request, the Driver splits each read into smaller requests.

Channel reference

The table shows the Console label of each setting, with its Python field under it.

Setting Default Notes
Channel name name Empty The name of the channel that the Console creates.
channel The key of the channel that records the values.
Node ID node_id See node IDs.
field Empty The field of a structure node. See structure fields.
Node name node_name Empty The browse name, or the folder path. Names the channel when the name is empty.
data_type float32 The data type of the channel that the Console creates.
Use as index is_index Off Shows only for a DateTime node. See server timestamps.
Enabled disabled Off A disabled channel is not read.

Data types

The Console creates each channel with the data type of its node:

OPC UA type Synnax data type
Boolean boolean
SByte int8
Byte uint8
Int16 int16
UInt16 uint16
Int32 int32
UInt32 uint32
Int64 int64
UInt64 uint64
Float float32
Double float64
String string
DateTime timestamp
Guid uuid
ByteString bytes
Enumeration int32

A channel can have a different data type than its node. The Driver converts each value to the data type of the channel, and a value that does not fit is a bad value.

Troubleshooting

  • Invalid NodeId format
    Cause

    The node ID is not in a form that the Driver accepts.

    Fix

    Write the node ID in one of the forms in node IDs.

  • Received bad values
    Cause

    The server sent a Bad status for a node, the server has no namespace with the URI of the node, or the Driver could not convert its value. The description names each channel and the reason. For example, BadNodeIdUnknown means that the server has no node with that ID. See bad values.

    Fix

    For BadNodeIdUnknown or a missing namespace, drag the node from the Browser again. For a conversion error, check the data type of the node.

  • Received uncertain values
    Cause

    The server is not sure that a value is correct, such as a last usable value of a sensor. The task records the value.

    Fix

    Check the device that the server reads the node from.

  • Failed to read data
    Cause

    The task lost the connection to the server. It tries again until the server answers. See outages.

    Fix

    Check the server connection.

  • OPC UA array for ... is too small... is too large
    Cause

    An array node has a different number of values than Array size.

    Fix

    Set Array size to the length of the array.

  • Channel ... already exists as ...
    Cause

    Another task already reads the node into that channel.

    Fix

    Move the channels to one task.

  • Failed to browse OPC UA nodesFailed to find variables
    Cause

    The Driver could not browse the server, or the folder that you dragged into Channels. A node that fails while the rest of the tree loads shows instead.

    Fix

    Check the server connection.

  • Failed to read node
    Cause

    The Driver could not read the details of the node. For BadNodeIdUnknown, the server has no node with that ID.

    Fix

    Check the node ID that you entered, or select the node in the Browser again.