Next
ReferenceHardwareModbusRead task

Modbus read task

Read the coils and registers of a Modbus TCP server into channels.

A Modbus read task reads coils and registers from one Modbus server into channels. For example, it can record a tank level from holding registers 0 and 1 of a PLC at 10 Hz.

Before you start, you need a connected server.

Registers and coils

A read task reads four types of data, each with its own address range:

Console label Modbus name Function code Value
Coil Coil 01 0 or 1
Discrete Discrete input 02 0 or 1
Holding register Holding register 03 A number, in 1 to 4 registers
Register Input register 04 A number, in 1 to 4 registers

A register holds 16 bits. An 8-bit or 16-bit value uses one register, and an 8-bit value is the low byte. A 32-bit value uses two registers, and a 64-bit value uses four. The Data type of the channel sets the size. A bit channel reads one bit of a register, and a string channel reads two characters from each register.

For each type, the Driver reads the addresses of the task in as few requests as it can. One request holds at most 125 registers or 2000 coils or discrete inputs. A request also reads the addresses between your channels, up to the Max gap of the server. Lower Max registers or Max gap for a device that rejects long reads or unused addresses.

The Driver timestamps each read with the computer clock. See timing.

Byte and word order

By default, the Driver reads the low word of a 32-bit or 64-bit value first (word swap, CDAB). Many devices send the high word first (big-endian, ABCD). The Byte order of the server sets the order for every register channel of the server.

To change the order of one channel, use its Bytes and Words selects. Each select has three options:

  • device -> uses the byte order of the server, and shows its value, such as device (swapped).
  • swapped -> swaps the order of this channel, whatever the server sets.
  • not swapped -> does not swap the order of this channel, whatever the server sets.

The Console hides Words for 8-bit and 16-bit data types, because they fit in one register. In code, leave bytes_swapped and words_swapped unset to use the order of the server.

Create a Modbus read task

Enterprise
  1. In the devices toolbar, right-click the server and select Create read task.
  2. Set Sample rate and Stream rate.
  3. Click Add channel. Select the type, then enter the address. For a register, select the Data type. For a string, set the Length. For a bit, set the Bit.
  4. Click (Start).

The Console creates the channels. For the server Pump skid PLC, a float32 holding register at address 0 gives Pump_skid_PLC_holding_register_input_0_f32, and a coil at address 3 gives Pump_skid_PLC_coil_input_3. The index channel is Pump_skid_PLC_time.

Task options

Console label Python field Default Notes
Modbus server device The key of the server.
Sample rate sample_rate 10 Hz How often the Driver reads the server. Up to 50,000 Hz.
Stream rate stream_rate 5 Hz See read tasks.
Data saving data_saving_disabled On See data saving.
Auto start auto_start Off Starts the task each time the Driver starts.

Channel reference

Each channel has an address, from 0 to 65535, and a channel, the Synnax channel that records the value. Each table shows the Console label of a setting, with its Python field under it.

The Console also accepts a six-digit Modicon address, such as 300001 for input register 0. The first digit is the table: 0 for coils, 1 for discrete inputs, 3 for input registers, and 4 for holding registers. The Console shows the Modicon form next to each address.

Coil

Python CoilReadChannelTypeScript coil

Reads a coil as 0 or 1, as uint8.

Strings

Each register holds two characters, the high byte first. Bytes set to swapped puts the low byte first. The string ends at the first NUL character. The Synnax channel of a string must have the string data type.

Troubleshooting

“Illegal data address”

The server does not have one of the addresses in a request. The error names the channels and the addresses of the request. Check the address map of the device. Some devices count addresses from 1, so try the address minus 1. If the server does not have the addresses between two channels, set Max gap of the server to 0.

“unsupported data type: …”

The Driver does not support the data type of the channel. Select a data type from the channel reference.

The values are wrong

Set the byte and word order of the server or the channel. Check that the data type matches the device.

The connection dropped

The Driver reconnects and sends the request again at once, up to the Retries of the server. If that fails, the task keeps running and shows the warning “Failed to read data”. The Driver tries again, up to every 5 seconds, until the server is back.

For other problems, see Connect a Modbus server and Troubleshoot hardware.