# Connect a Modbus server

> Connect a Modbus TCP or Modbus RTU server, such as a PLC or an I/O module, to Synnax.

The Modbus integration reads and writes the coils and registers of Modbus TCP servers and of Modbus RTU servers on a serial port, such as PLCs and remote I/O modules. Modbus ASCII and Modbus RTU over TCP are not supported. In Synnax, a Modbus server is one unit at an IP address and port, or on a serial port. The [read task](https://docs.synnaxlabs.com/reference/hardware/modbus/read-task) and the [write task](https://docs.synnaxlabs.com/reference/hardware/modbus/write-task) add the addresses.

To reach several units behind one gateway or on one serial line, connect one server for each unit, with the same address and a different unit ID. Servers on the same host and port, or on the same serial port, share one connection, and their requests take turns.

## Prerequisites

* Supported

  WindowsmacOSLinuxDocker

* Not supported

  NI Linux RT

- A running Driver that can reach the server on the network. Synnax Desktop runs one for you.
- For a serial device, a Driver on the computer that the serial adapter connects to. An RS-485 adapter must switch its transmit direction by itself, as most USB adapters do.

## Connect a server

[Enterprise](https://docs.synnaxlabs.com/reference/get-started/editions "Needs Synnax Enterprise")

**Console**

1. In the [devices toolbar](https://docs.synnaxlabs.com/reference/hardware/devices#devices-toolbar), click (**Connect device**), then select **Modbus server**. You can also run the “Connect Modbus server” command.
2. Enter a name for the server.
3. In **Transport**, select **TCP** for a server on the network, or **Serial** for a device on a serial port.
4. For TCP, enter the IP address or hostname of the server in **Host**, such as `192.168.1.20`, and its port in **Port**. The default port is `502`.
5. For serial, enter the port in **Serial port**, such as `/dev/ttyUSB0` on Linux or `COM3` on Windows. Then select the **Baud rate**, **Parity**, and **Stop bits** of the device.
6. In **Connect from**, select the Driver that connects to the server. If only one running Driver has Modbus enabled, the Console selects it for you.
7. On the **Unit** tab, enter the **Unit ID**. Keep `255` for a TCP server you reach directly. For a unit behind a gateway or on a serial line, enter its unit ID.
8. In **Byte order**, select the order in which the device sends its bytes. See [byte and word order](https://docs.synnaxlabs.com/reference/hardware/modbus/read-task#byte-and-word-order).
9. If the device is slow or limits its requests, change the settings on the **Advanced** tab. See [connection options](https://docs.synnaxlabs.com/reference/hardware/modbus/connect-server#connection-options).
10. Click **Connect**.

The Console asks the Driver to read holding register 0 of the unit before it saves the server. Any reply, an error reply included, shows that the unit answers. If the unit does not answer, the dialog shows the error and keeps your entries.

[](https://synnax.nyc3.cdn.digitaloceanspaces.com/docs/device-drivers/modbus/connect-server/modbus-connect/15e4500b0be9-dark.mp4#t=0.001)

**Python**

```python
from synnax import modbus

rack = client.racks.retrieve_embedded_rack()
device = client.devices.create(
    modbus.Device(
        name="Pump skid PLC",
        host="192.168.1.20",
        port=502,
        location="192.168.1.20:502",
        rack=rack.key,
        configured=True,
    )
)
```

For a serial device, pass `transport="rtu"` and the line settings:

```python
device = client.devices.create(
    modbus.Device(
        name="Flow meter",
        transport="rtu",
        serial_port="/dev/ttyUSB0",
        baud_rate=9600,
        parity="none",
        unit_id=3,
        location="/dev/ttyUSB0",
        rack=rack.key,
        configured=True,
    )
)
```

Python does not test the connection. Pass the key of a rack, or the device has no Driver. Pass `configured=True`, or the Console asks you to configure the server.

**TypeScript**

```typescript
const rack = await client.racks.retrieve({ name: "Node 1 Embedded Driver" });
await client.devices.create({
  key: crypto.randomUUID(),
  name: "Pump skid PLC",
  rack: rack.key,
  location: "192.168.1.20:502",
  make: "Modbus",
  model: "Modbus",
  configured: true,
  properties: {
    connection: { host: "192.168.1.20", port: 502, swapBytes: false, swapWords: false },
    read: { index: 0, channels: {} },
    write: { channels: {} },
  },
});
```

For a serial device, set `connection` to the serial fields:

```typescript
connection: {
  transport: "rtu",
  serialPort: "/dev/ttyUSB0",
  baudRate: 9600,
  parity: "none",
  stopBits: 1,
  unitId: 3,
  swapBytes: false,
  swapWords: false,
},
```

TypeScript does not test the connection.

After you connect a server, the Driver checks the unit every few seconds and shows the result as the server status in the devices toolbar. If a task got a reply from the unit since the last check, the Driver sends no request. Otherwise it reads holding register 0. See [device statuses](https://docs.synnaxlabs.com/reference/hardware/devices#statuses).

## Connection options

| Console label     | Python field               | Default               | Notes                                                                                                                |
| ----------------- | -------------------------- | --------------------- | -------------------------------------------------------------------------------------------------------------------- |
| Transport         | `transport`                | `tcp`                 | `tcp` for Modbus TCP, or `rtu` for Modbus RTU on a serial port.                                                      |
| Host              | `host`                     |                       | TCP only. An IPv4 address, an IPv6 address, or a hostname.                                                           |
| Port              | `port`                     | `502`                 | TCP only. Python has no default.                                                                                     |
| Serial port       | `serial_port`              |                       | RTU only. Such as `/dev/ttyUSB0` or `COM3`.                                                                          |
| Baud rate         | `baud_rate`                | `19200`               | RTU only. See [serial devices](https://docs.synnaxlabs.com/reference/hardware/modbus/connect-server#serial-devices). |
| Parity            | `parity`                   | `even`                | RTU only. `none`, `even`, or `odd`.                                                                                  |
| Stop bits         | `stop_bits`                | `1`                   | RTU only. `1` or `2`.                                                                                                |
| Connect from      | `rack`                     |                       | The Driver that connects to the server.                                                                              |
| Unit ID           | `unit_id`                  | `255`, or `1` for RTU | The unit that requests go to: 0 to 255 for TCP, and 1 to 247 for RTU.                                                |
| Byte order        | `swap_bytes`, `swap_words` | Word swap             | See the table below.                                                                                                 |
| Timeout           | `timeout_ms`               | `1000`                | The time to connect, and to wait for each reply, in milliseconds.                                                    |
| Retries           | `retries`                  | `1`                   | How many times the Driver sends a request again at once after a fault.                                               |
| Request delay     | `delay_ms`                 | `0`                   | The wait between requests on the connection, from 0 to 5000 milliseconds.                                            |
| Max registers     | `max_registers`            | `125`                 | The most registers in one read, from 1 to 125.                                                                       |
| Max gap           | `max_gap`                  | `125`                 | The widest gap between channels that one read spans. `0` reads only yours.                                           |
| Write codes       | `write_codes`              | `multiple`            | `multiple` writes with function codes 15 and 16. `single` uses 05 and 06.                                            |
| Mask write (FC22) | `mask_write_supported`     | `false`               | Bit writes in a holding register use function code 22, in one request.                                               |

**Byte order** sets the order of every register channel of the server. A channel can override it. The letters show the bytes of a 32-bit value in the order the device sends them, with A the most significant byte.

| Byte order           | `swap_bytes` | `swap_words` |
| -------------------- | ------------ | ------------ |
| Big-endian (ABCD)    | `False`      | `True`       |
| Byte swap (BADC)     | `True`       | `True`       |
| Word swap (CDAB)     | `False`      | `False`      |
| Little-endian (DCBA) | `True`       | `False`      |

A request that times out or loses its connection is sent again at once, up to **Retries** times. When the unit does not reply to three attempts in a row, the Driver stops sending requests to it for 10 seconds, so that a unit that is off does not slow down the other units on the connection. A connection that fails does not count toward the three.

## Serial devices

All servers on one serial port must use the same line settings. When a task or a check uses a server whose settings differ from the settings in use on the port, it fails with an error that names both. The Driver always uses 8 data bits, as Modbus RTU requires. The baud rate is one of 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, or 230400, the rates that the Driver can set on Linux, macOS, and Windows. Between two requests, the Driver waits for the silence of 3.5 characters that Modbus RTU requires, or 1.75 ms above 19200 baud.

On Linux, the user that runs the Driver needs access to the serial port. This usually means that the user is in the `dialout` group.

## Troubleshooting

### Connect fails with “Connection refused” or a timeout

Check the address and the port. Make sure that the server allows Modbus TCP connections from the computer that runs the Driver.

### Connect fails with “Connection timed out”, but the server is on

The server accepts the connection, but the unit does not answer. Check the **Unit ID**. A gateway needs the unit ID of the device behind it. Some servers answer only unit 1 or unit 0.

### “Gateway target device failed to respond”

The gateway is on, but the unit behind it does not answer. Check the unit, its wiring, and the **Unit ID**.

### Connect fails with “No such file or directory”

The serial port does not exist on the computer that runs the Driver. Check the port name and that the adapter is plugged in.

### Connect fails with “Permission denied”

The Driver cannot open the serial port. On Linux, add the user that runs the Driver to the `dialout` group.

### A serial device does not answer

Check that the baud rate, parity, and stop bits match the device, and that the device uses 8 data bits. On an RS-485 line, check that the A and B wires are not swapped.

For other problems, see [Troubleshoot hardware](https://docs.synnaxlabs.com/reference/hardware/troubleshooting#failed-to-reach-device-or-failed-to-reach-server).